©Westermo Teleindustri ABUser Guide6651-22611Industrial Converter PROFIBUS DP to Fibre Optic Link Repeater, line and redundant ringwww.westermo.comOD
106651-22611Optical fibre link functionality and status indicationAt power on, all LED's will be active during an initiation sequence followed by
116651-22611Note tbit = 1 / Baud rate (Baud rate in bit/s)System delay in an optical networkData exchange between a PROFIBUS DP master and slave via O
126651-22611Multidrop, one data exchange • The data exchange between PROFIBUS DP master and slave via ODW-610-F2 fibre optic link will run from the
136651-22611Interface specifications* External supply current capability for proper startup PowerRated voltage 12 to 48 VDC 24 VACOperating voltag
146651-22611Optical Power BudgetThe maximum supported link lengths as specified in the table above should only been seen as indicative. The allowed li
156651-22611DIP-switches accessible under lid (for details see page 17-18)LED Indicators (for details see page 16) FX(Fibre) (for details see page 1
166651-22611LED Indicators* Time and number of frames are set by DIP-switch S:2.LED Status DescriptionPWR PowerON In service (power).Flashing Fault co
176651-22611S1 DIP-switchDIP-switch settingsBefore setting DIP-switches:Prevent damage to internal electronics from electrostatic discharges (ESD) by
186651-22611S1 DIP-switchS2 DIP-switchDescriptionON 1 2 3 4 5 6 7 8ON 1 2 3 4 5 6 7 81 faulty frame before data rate is seen as unidentified.
196651-22611CoolingThis unit uses convection cooling. To avoid obstructing the air-flow around the unit, use the following spacing rules. Minimum spac
26651-22611Legal informationThe contents of this document are provided “as is”. Except as required by applicable law, no warranties of any kind, eithe
206651-22611Start up guideRedundant ring applicationFollow the steps below to get the unit up and running in a simple application. Ring ARing BTX RX T
216651-22611Multidrop applicationFollow the steps below to get the unit up and running in a simple application. TX RX TX RX TX RX TX RX TX RX TX RX T
226651-22611HintsIf the fibre distance is long it may be necessary to adjust the bus parameter Slot time, the monitoring time (tbit) of the sender of
REV.A 6651-22611 2012-12 Westermo Teleindustri AB, Sweden – A Beijer Electronics Group CompanyWestermo • SE-640 40 Stora Sundby, SwedenTel +46 16
36651-22611SafetyBefore installation:Read this manual completely and gather all information on the unit. Make sure that you understand it fully. Check
46651-22611Note. Fibre Optic HandlingFibre optic equipment requires careful handling as the fibre components are very sensitive to dust and dirt. I
56651-22611Declaration of Conformity Westermo Teleindustri AB Declaration of conformity Org.nr/ Postadress/Postal address Tel. Telefax Pos
66651-22611Type tests and environmental conditionsElectromagnetic CompatibilityPhenomena Test Description LevelESD EN 61000-4-2 Enclosure contact ± 6
76651-22611Functional description Internal Electronics COM COM +VA OVP +VB C NO NC STATUS POWER LED’s OV P OC P RxD/TxD - P R
86651-22611Redundant ring via fibre optical networkUnder normal operation the PROFIBUS DP data is sent over ring A. Should a fault be detected on the
96651-22611… Recovery from faulty status • ODW-610-F2 will automatically recover to the previous operating status when a failure disappears. This