©Westermo Teleindustri ABUser Guide6651-22651www.westermo.comIndustrial Converter RS-485 to Fibre Optic Link Repeater, line and redundant ringODW-630-
106651-22651Multidrop via fibre optical networkThe data is transferred via the fibre optic network to the serial ports of all units. If ODW-630-F2 is
116651-22651Optical fibre link functionality and status indicationAt power on, all LED’s will be active during an initiation sequence followed by an a
126651-22651System delay in an optical networkData exchange between a serial master and slave via ODW-630-F2 fibre optic link, will be delayed due to
136651-22651Example• Redundant ring, one data exchange between master and one slave. One a master and 11 slaves with data rate 9600 bit/s dependent m
146651-22651Status Port type Signal relay, changeover contactsRated voltage Up to 48 VDCOperating voltage Up to 60 VDCContact rating 500 mA @ 48 VDCCo
156651-22651FX (Fibre) SM-LC80 SM-LC40 SM-LC15 MM-LC2Fibre connector LC duplex LC duplex LC duplex LC duplexFibre type Singlemode 9/125 mmSinglemode 9
166651-22651Location of Interface ports, LED’s and DIP-switchesPosition Direction* Description Product marking1 In Common voltage COM2 In Voltage A +V
176651-22651LED indicators LED Status DescriptionPWR PowerON In service (power)Flashing Fault conditionOFF Out of serviceRDR ON Redundant ring modeOFF
186651-22651ConfigurationAll needed configurations and parameter settings are done by the DIP-switches, located under the top lid.!DIP-switch settings
196651-22651S2 DIP-switchON 1 2 3 4 5 6 7 8Set status interface at local fibre link error*Factory settingsON 1 2 3 4 5 6 7 8S1ON 1 2 3 4 5 6
26651-22651Legal informationThe contents of this document are provided “as is”. Except as required by applicable law, no warranties of any kind, eithe
206651-22651SW:1 SW:2Transmitter ONON 1 2 3 4 5 6 7 8ON 1 2 3 4 5 6 7 81.6 msON 1 2 3 4 5 6 7 8ON 1 2 3 4 5 6 7 8416 µsON 1 2 3 4 5 6 7
216651-22651RS-485 termination at system levelThe system should be installed in according to the RS-485 specification. A system should always form a
226651-22651CoolingThis unit uses convection cooling. To avoid obstructing the air-flow around the unit, use the following spacing rules. Minimum spac
236651-22651Prepare the master unitsConfigure network, with master and slaves. Check that it is running correctly with the …electrical serial network
246651-22651Multidrop applicationFollow the steps below to get the unit up and running in a simple application. Prepare the unitsConfigure the network
256651-22651Unit 1 Unit 2 Unit 3CH2 Bi-di 1550 nm Bi-di 1550 nm Bi-di 1550 nmCH1 Bi-di 1310 nm Bi-di 1310 nm Bi-di 1310 nmUnit 1 Unit 2CH1 Bi-di 1310
266651-22651End unit 1 Unit 2 End unit 3CH2 – Bi-di 1550 nm –CH1 Bi-di 1310 nm Bi-di 1310 nm Bi-di 1550 nmMultidrop with Bi-di transceiversHintsIf the
REV.A 6651-22651 2012-12 Westermo Teleindustri AB, Sweden – A Beijer Electronics Group CompanyWestermo • SE-640 40 Stora Sundby, SwedenTel +46 16 4
36651-22651SafetyBefore installation:Read this manual completely and gather all information on the unit. Make sure that you understand it fully. Check
46651-22651Note. Fibre Optic HandlingFibre optic equipment requires careful handling as the fibre components are very sensitive to dust and dirt. I
56651-22651Declaration of Conformity Westermo Teleindustri AB Declaration of conformity Org.nr/ Postadress/Postal address Tel. Telefax Pos
66651-22651Type tests and environmental conditionsElectromagnetic CompatibilityPhenomena Test Description LevelESD EN 61000-4-2 Enclosure contact ± 6
76651-22651STATUS C NO NC LED’s Switches CH 2 SFP Fibre transceiver TX RX CH 1 SFP Fibre transceiver TX RX Internal Electronics ODW-630F2 COM
86651-22651Designed for harsh environments, such as industrial, road and railway applicationsODW-630-F2 complies with standards for industrial enviro
96651-22651Failure IndicationsFibre interruption ring A, TX On: FL RFibre interruption ring A, RX On: FL L Fibre interruption ring A, RX & TX On F