Westermo ODW-631 User Manual Page 23

  • Download
  • Add to my manuals
  • Print
  • Page
    / 26
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 22
23
6650-2243
Configure the ODW-631.
S1: 2-wire RS-485. Data rate, asynchronous mode must be set by S1.
S2: Asynchronous mode or Synchronous mode.
S3: Termination and fail-safe of the RS-422/485 port.
Connect the fibre link between the ODW-631s.
Connect the power supply to both ODW-631s.
After a few seconds the fibre link should be in operation, indicated by an active CH1
LED.
Connect the serial cables from PLC master and slave to respective ODW-631s.
Frames from PLC master that are correctly received in the ODW-631 will be
indicated by flashing TD LED.
Frames that are received via the fibre link will be transmitted to the PLC slave
and indicated by flashing RD LED.
Replies from slave to master will be transferred and indicated in the opposite way.
The point-to-point application is up and running.
POWER CH 1
COM +VA +VB COM
POWER CH 1
COM +VA +VB COMTX RX TX RX
Start up guide, point-to-point application
Follow the steps below to get the unit up and running in a simple application.
Master Slave