Industrial Ethernet adapter– Serial Server (TCP)INSTALLATION MANUAL6609-2211www.westermo.comED-10 TCP©Westermo Teleindustri AB • 2001 • REV. BGalvanic
Pin Signal Name*Number Description V.24 RS-232CDirection** Description1 DCD 109 CF Out TCP connection established2 RD 104 BB Out Received Data3 TD 103
116609-22112-wire termination4-wire termination5.2.1 RS-422/485 general advice=TerminationED-10 Slave unit Slave unit Slave unitED-10 Slave unit Slave
12 6609-2211CH2: RS-232 Connections (D-sub connector), DCECH1 and CH2 are not galvanic isolated.Please use a RS-232 isolator (e.g. MD-52) if earth vol
136609-22115.3 Configuration5.3.1 DIP switch settingsDIP-switches used to configure the modem are accessable under the lid on top/front of the unit.Wa
Termination and fail safe(4-wire) Channel 114 6609-2211Restore default settingsChannel 2ON12345678S2Normally in this positionON12345678S2Restore defau
156609-22115.3.2 LED'sCH1: TD Transmitted Data (incoming serial data):LED off • RS-232 TD = 1, Mark (< –3V) / RS-422/485 = 1, Mark (R+ < R–
16 6609-22115.4 Installation of ED-ToolThis section describes the installation of ED-Tool.System Requirements:To install and run the ED-Tool program f
176609-22116. Functional descriptionThe ED-10 TCP can be in either configuration (config) mode or in application (app) mode.Normally the ED-10 TCP is
18 6609-2211The ED-10 TCP network performance can be optimized for minimum delays or minimumnetwork loading. By default it is optimized for minimum de
196609-22117. Configuration7.1 Configuration by ED-ToolED-Tool is intended to be used with a number of products.This section describes ED-Tool program
20 6609-2211Program Start:To start ED-Tool• Locate ED-Tool under Program on the Windows Start Menu.• Click on the ED-Tool icon• Or locate the ED-Tool
216609-2211ED-Tool commandsThis section describes the ED-Tool commands to be used together with the product ED-10 TCP.The commands can be executed by
22 6609-22117.2 Configuration by terminalED-10 TCP internal commands must be used to configure by terminal program.TYPE commandConfiguration parameter
EXAMPLE 1Example of how to force the ED-10 TCP into config. mode, change some parametersand then reboot into application mode with the changed paramet
24 6609-22117.2.1 Local configurationRemove any device connected to serial interface CH1 and connect to ED-10 TCP serialinterface CH2: RS-232 at 19 20
256609-22117.3 Configurable parametersConfigurable parameters are summarised in the following tables. A more detaileddescription follows. Parameter na
26 6609-2211ParameterLocal IP AddressGateway IP AddressSubnet MaskLocal ProtocolPortRemote IP AddressRemote Protcol PortTelnet UserNameTelnet Password
276609-22117.3.1. Serial interfaceData RateThe data rate can be set from 300 bit/s to 115.2 kbit/s.Default is 19 200 bit/s.Data BitsSeven (7) or eight
28 6609-22117.3.2. Packing algorithmEnd of frame character, EoF CharASCII code of character indicating end of frame (0-255). The serial data buffered
296609-22117.3.3. Network interfaceLocal IP address*Local IP address is used as the first part of local end point identity, in both applicationand con
36609-2211Contents1. Introduction ...
30 6609-2211Gateway IP address*The Gateway IP address is used for indirect delivery of network packets when theRemote IP address is not a part of the
316609-22118. Application examplesThis application can be achieved using one of the methods described in section 1.For solution 1 Telnet can be found
T03-0390 • 6609-2211 03.07 Mälartryck AB, Eskilstuna, SwedenWestermo Teleindustri AB • SE-640 40 Stora Sundby, SwedenPhone +46 16 42 80 00 Fax +46 16
4 6609-22111. IntroductionThe ED-10 TCP is an Industrial Ethernet Adapter acting as a serial server. The type ofserial interface is selectable between
56609-2211The ED-10 TCP is ideal for use in the industrial environment.It is housed in the Westermo DIN rail box and has a wide range power input, iso
6 6609-22113. SpecificationNetwork Interface 10BASE-T. IEEE std 802.3, 2000 Edition. Data rate 10 Mbit/s, half duplex.Mechanical RJ-45 Modular Jack (I
76609-2211Configuration Remotely over Network or locally at serial interface.Windows based PC-programme or simple terminal programme.Indicators (LED)
8 6609-22114. MaintenanceNo maintenance is required,as long as the unit is used within the specified conditions.5. Installation5.1 Mounting / RemovalB
96609-2211CH1:RS-422/485Screw terminalCH1:RS-232 D-subPower screw terminalCH2: RS-232 D-subconfiguration onlyNetworkRJ-45 connection5.2 ConnectionsCH1