Westermo RM-115S User Manual Page 38

  • Download
  • Add to my manuals
  • Print
  • Page
    / 57
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 37
115S Serial I/O Module User Manual
Page 38 June 2011
4.5.2 Current output
Current outputs may be selected in the scales 0 to 10mA, 0 to 20mA, or 4 to 20mA. For
each scale, the minimum to maximum signal levels are represented by 4000 hex to C000
hex. Table 4-4 shows how signals from other ELPRO products translate to 115S-13
current levels.
115S-13
Current scale
105-1
Input current
(mA)
105-2
Input current
(mA)
105-G
Register value
(hex)
115S-13
Output current
(mA)
0 to 10mA
4
4
4000
0
20
20
C000
10
0 to 20mA
4
4
4000
0
20
20
C000
20
4 to 20mA
N/A
*
0
2000
0
2
*
2
3000
2
4
4
4000
4
20
20
C000
20
Table 4-4: Compatibility of other ELPRO products with 115S-13 voltage outputs.
*
Reduced accuracy for less than 4mA in 105-1.